Float Level Controller-BCL  
Model BCL float level Controller develop by BNC from many years ago, Suitable for boiler level control,and other liquid Vessel, storage tank application.  
   

Principle: BNC level controller install on the top side near by a level moniter tube, when water level to go up or down, the float will follow up, then connect to the magnetic will also follow up, there have a S.S. tube to be isolate the pressure side and control side, inside of controller can install 1~6 sets of magnetic switch, when the level up on down, the magnetic switch will colse open, connect the these control point to control panel or pump, it's will control the boiler and moniter the level control for alarm system.

 

 
Specification:
Control point: 1~6 point  
Distance form each point to another: 15mm (minimum)  

Mat't: Cast Iron, Stainless steel

 
Max. pressure: 25 Bar  
Max.Temp.: 250 oC  
Conctact Capability: 250VAC,2A  
Enclosure: IP65  

 

Model NO.Table

Basic
Model
Flange
Rating
Flange
Mat'l
Switch Unit
Description
BCL
 
 
 
 
-A
1
 
 
ANSI 150 #RF
2
 
 
ANSI 300 #RF
-J
1
 
 
JIS 10K RF
2
 
 
JIS 20K RF
3
JIS 30K RF
-D
1
 
 
PN 16 RF
2
 
 
PN 25 RF
1
 
SF45
2
 
SUS 304
3
 
SUS 316
-1
With 1 Switch
-2
With 2 Switches
-3
With 3 Switches
-4
With 4 Switches
-5
With 5 Switches
-6
With 6 Switches

 

 

 
   
Dimension

 
   

 

Catalog Download